| TING MANUAL |
| |
- Low Energy
- Low X-Ray Flux
- No X-Ray Flux
- Multiple discharges on thyratron
- Multiple X-Ray pulses per trigger pulse
- Discharge has streamers
- H.V. enable external interlock light is not on
- Filament ready light will turn on
- Circuit breaker on M04 keeps tripping
- Only one bank of thyratrons fires
- One rail gap does not fire
- Circuit breakers on thyratron banks keep tripping
- Blowing fuses in MO
|
| |
| I. Low Energy |
A. Good ASE
Things to check:
- There is SF6 gas pressure in the rail gaps
Make sure the SF6 gas cylinder is not empty and that the tank and the regulator
valves are open. The SF6 gas pressure gauge on the control rack should now read
~ 40 psi.
- The seed pulse has adequate energy
Measure the 248nm energy of the seed pulse after the vacuum spatial filter after
the excimer. If the energy is less than 100 J then check the seed pulse.
- The seed pulse is correctly timed with Prometheus
Look at the Prometheus photodiode on the digital scope.
Make sure the setup on the scope is setup 9. See if the seed pulse is riding
on top Prometheus ASE.
- The seed pulse has good energy when Prometheus fires
Look at the 248nm energy of the seed pulse coming through the vacuum spatial
filter after the excimer. Make sure that there is no consistent drop in this energy
when Prometheus fires. This checks to see if there is noise B. Bad ASE
Things to check:
- Both thyratron banks are firing
Look to see that every thyratron in both banks flashes when Prometheus fires.
- Railgaps are firing
Look through the four windows in the HV enclosure doors to see that each one
of the railgaps fires.
- Gas mix
Change the gas if it is old. |
| Top |
| II. Low X-ray flux (as measured with the x-ray detector) |
Things to check:
- X-ray voltage reading on high voltage control unit meter
The voltage on this meter should be charging to ~ 145 kV.
- Relative timing between anode and cathode monitor
If the relative timing is off, the x-ray flux will suffer. Look at both the anode
monitor and the cathode monitor on the scope at the same time. Trigger the scope
sweep off of the rising edge of the anode waveform.
- Anode monitor waveform
- Cathode monitor waveform
Possible causes:
Spark gap boards need to be cleaned |
| Top |
| III. No X-ray flux |
Things to check:
- Thyratron in an oil tank is firing
If the thyratron is getting a trigger signal, you should be able to hear the
thyratron click when it fires.
- 30 kV power pack in x-ray power supply oil tank
Check the output with a high voltage probe and a scope. The voltage should be
a 30 kV DC source.
- Broken connections on thyratron anode
Drain the oil out of the x-ray high voltagepower supply tank and check all of
the connections to make sure that there are not any loose connections.
- Broken connections on pulse transformer
Make sure that the output from the secondary of the transformer to the x-ray
gun anode is still connected. |
| Top |
| IV. Multiple discharges on thyratron bank |
Possible causes:
- Loose connections on thyratrons
Make sure that the screw connections on the thyratron anodes have not come loose.
- One or more thyratrons are bad
|
| Top |
| V. Multiple X-ray pulses per trigger pulse |
Possible causes:
- Inappropriate heater and reservoir voltages on thyratron.
This should only affect the jitter of the x-ray emission relative the trigger
pulse. One can adjust these voltages in the x-ray anode thyratron heater and reservoir
power supply unit.
- Bad HY3202 thyratron
Look at the trigger waveforms to the thyratron.
- Bad timing board in the X-ray thyratron power supply.
Swap this board with a space and see if problem disappears. |
| Top |
| VI. Discharge has streamers |
Things to check:
- There is SF6 gas flow to rail gaps
Make sure the SF6 supply valve at the rail gaps control rack is open. Make sure
the SF6 gas cylinder is not empty and that the tank and the regulator valves are
open. The SF gas pressure gauge on the control rack should now read ~40 psi.
- X-ray flux
Check the x-ray flux with the x-ray meter and compare these readings with the
ones in the Prometheus notebook.
- Rail gaps are working properly
Make sure that all of the rails fire on every shot.
- Timing between anode and cathode is optimum
If the relative timing is off, the x-ray flux will suffer. Look at both the anode
monitor and the cathode monitor on the scope at the same time. Trigger the scope
sweep off of the rising edge of the anode waveform.
- Timing between anode and modulators is close
If the relative timing is off, the laser will try to discharge through the gas
without the gas being sufficiently ionized. Trigger the scope off the rising edge
of the x-ray anode monitor (Amon). The falling edge of the modulator monitor (NDO)
should occur near the peak of the anode waveform. One can change the timing by
changing the delay on channel D of the Stanford digital delay box. One can optimize
this timing by looking at the ASE only from Prometheus and scan channel D on the
Stanford digital delay box to maximize the ASE pulse. |
| Top |
| VII. H.V enable ext. interlock light is not on |
Possible causes:
- Timing module in timing rack is out of sync
Make sure that the Ti: Sapphire oscillator is modelocked. Press the button on
pulse frequency divider #3 box until the lasers are synchronized (the green LED
on the sync box turns on). |
| Top |
| VIII. H.V enable ext. interlock light is not on |
Possible causes:
- Filament switch on control unit is not on
Make sure this toggle switch is on (the up position).
- Circuit breaker on M04 has been tripped
M04 is on the northeastern part of the top of Prometheus. The circuit breaker
consists of three circuit breakers tied together (one for each phase of 120VAC).
Make sure this circuit breaker is in the up position.
Things to check:
- FVoltage meter on M04 front panel
M04 is on the northeastern part of the top of Prometheus. There is an aluminum
box with an ammeter readings match the numbers printed on the aluminum box. |
| Top |
| IX. Circuit breaker on M04 keeps tripping |
Possible causes:
- bad high current diode
Check each of the six high current diodes to see if one is shorted out or open. |
| Top |
| X. Only one bank of thyratrons fires |
Possible causes:
- No trigger signal
Check to make sure there is a +15v trigger signal going to the thyratron banks.
- Small thyratron is bad (not switching)
Check to see if the small thyratron banks fires (flashes) when the thyratron
bank is triggered.
- No switching voltage
Check the 15kV power pack in each bank with a high voltage probe and scope to
make sure that there is 15kv DC.
- The resistor from the anode of the small thyratron to the power pack is open
Check the resistance of the 1M pencil resistor. Also, make sue that the capacitors
are not shorted internally or leaking oil. |
| Top |
| XI. One rail gap does not fire |
Possible causes:
- Silicon oil contamination inside rail gap
There might be silicon oil inside of the rail gap box. You need to empty the
oil out of the HV enclosure and lower the doors to be able to check this for sure.
- HV cable is not delivering voltage to the rail gap
For this procedure you need to empty the oil out of the HV enclosure and lower
the doors. Then put a grounding stick near (~5mm) the place where the HV cable
connects to the gaps. Fire the rail gaps. The idea is that if the trigger pulse
arcs from the cable to the grounding stick, the cable is OK. |
| Top |
| XII. Circuit breakers on thyratron banks keep tripping |
Possible causes:
- The HV DC power pack is bad
Check the 15kV power pack in each bank with a high voltage probe and scope to
make sure that there is 15kv DC.
- The resistors or capacitors connected to the power pack are bad
Check the resistance of the 1M pencil resistor. Also, make sure that the capacitors
are not shorted internally or leaking oil. |
| Top |
| XIII. Blowing fuses in MOO (primarily the middle fuse) |
Possible causes:
- The charging current to the modulator power supply is too large.
Check the charging current through the M03 transformer. This should be ~40 Amps,
certainly less than 50 Amps. The clamp-on ammeter should show relatively smooth
current draw, not one or two large jumps. |
| Top |